Physical removal
The gel membrane (approx. 10 nm size exclusion) holds back silt, colloids and most microorganisms, and lowers the turbidity of the water going to the UV reactor.
Technology · Optional add-on
Purus filters the water clear. An optional UV disinfection reactor, fitted after the Purus outlet, then inactivates the bacteria and viruses that remain. Two independent barriers, run by one control system, quoted as part of your Purus package.
A 72-second walk through the train: the Purus gel membrane, why clear water matters to UV, the UV reactor, the shared controls and how each Purus model is matched to a reactor.
UV light has to reach a microorganism to inactivate it. Suspended particles absorb and scatter the light, and a microbe sheltering behind or inside a particle can escape the dose. Putting Purus in front removes that shelter.
The gel membrane (approx. 10 nm size exclusion) holds back silt, colloids and most microorganisms, and lowers the turbidity of the water going to the UV reactor.
A measured UV dose damages the genetic material of bacteria and viruses that pass the filter, so they can no longer reproduce. No chemicals are added to the water.
One barrier removes, the other inactivates. Because they work in different ways, the train does not rely on any single step performing perfectly.
The reactor is fitted on the Purus outlet and wired into the Purus controller, so filtration and disinfection start, stop and alarm together.
316L stainless-steel reactor with a low-pressure UV lamp in a quartz sleeve and an internal flow mixer, so all of the water passes close enough to the lamp to receive the dose.
A sensor on the reactor viewport reads the UV intensity continuously, so a dirty sleeve, an ageing lamp or a drop in water quality shows up before it becomes a problem.
The Purus controller switches the UV system on and off and receives its lamp-fail and low-UV-intensity alarms. Alarms can also be passed to your BMS.
If disinfection is not proven, the treated-water outlet is held rather than passing water that has not received its dose.
UV reactors are sized to the peak flow through them and to the UV dose the application needs: 40 mJ/cm² for drinking and process water, 30 mJ/cm² for cooling-tower and other non-potable uses. The pairings below use the reactors’ rated flows at a UV transmittance of 85%, typical of town water. Purus filtrate is expected to be at or above that.
| Purus model | Design peak flow | Drinking & process water · 40 mJ/cm² | Cooling tower & non-potable · 30 mJ/cm² |
|---|---|---|---|
| Purus 20.1 | ~1.5 m³/h | Rated to 1.81 m³/h | Rated to 2.41 m³/h |
| Purus 50.2 | ~5.5 m³/h | Rated to 6.01 m³/h | Rated to 5.77 m³/h |
| Purus 100.5 | ~8.5 m³/h | Rated to 9.01 m³/h | Rated to 10.02 m³/h |
| Purus 100.20 | ~8.5 m³/h | Rated to 9.01 m³/h | Rated to 10.02 m³/h |
Planning selection only. The final reactor is confirmed by Blue Quest engineering against a measured UV transmittance of your Purus filtrate, your peak flow and the dose your application or regulator requires. Multi-vessel installs and higher flows use larger or multiple reactors.
Drinking-water and food and beverage process water, rainwater and bore supplies, washdown and reuse water, and cooling-tower make-up or recirculation where a microbial barrier is wanted.
UV treats the water as it passes and leaves no residual disinfectant behind. Where water is stored or reticulated, a residual may still be required. Like Purus, UV does not remove dissolved salts or metals.
Lamp replacement and quartz-sleeve cleaning are added to your Purus service schedule, at the intervals recommended for the reactor.
The same two barriers take the particle, colloid and microbial load off RO membranes, without chlorine reaching them. See how the three-barrier train works and the evidence behind it.
Tell us in your enquiry and the reactor is quoted with your Purus package after we confirm your flow and water quality.